Get a quote
EN ⌄
English简体中文Русский

HSY / HAOSHENG

Define the equipment scope for megawatt-scale storage

M3355 1.72MW / 3.355MWh Container Energy Storage System

M3355 combines 3355kWh rated stored energy with 1.72MW rated AC power for factory, solar and wind-storage projects. Coordinate the battery container, power conversion and distribution around the 550V AC interface, site and operating mode.

013.355 MWhRated stored energy
021.72 MWRated AC power
03LiFePO4Battery chemistry
M3355 1.72MW / 3.355MWh Container Energy Storage System — HSY OEM branding visualization; container equipment with original M3355 model and safety markings retained

M3355 container equipment, HSY OEM branding visualization.

04550 VRated grid voltage
05Modbus TCPCommunications
06Air coolingCooling

This is a megawatt-scale project system. Define delivered equipment, grid interface, protection and fire safety in the project design. Rated energy does not guarantee usable energy or fixed runtime.

Rated stored energy3.355 MWh
Rated AC power1.72 MW
Battery chemistryLiFePO4
Rated grid voltage550 V

Clear details for product selection

Separate battery and conversion equipment

The specification lists separate battery and power-conversion containers. Define whether the transformer, PCS, distribution, fire protection, installation and commissioning are included in the quotation.

A separate choice from the 1.044MWh multi-cabinet system

This 3.355MWh, 1.72MW container system is separate from HSY-1044K-F. Use the load profile, connection voltage and site conditions to define the solution; nominal energy alone does not guarantee runtime.

Full specifications

ItemSpecification / configuration
Model markingM3355
Rated stored energy3355 kWh
Rated AC power1.72 MW
Cells and arrangementLiFePO4 / 3.2 V / 280 Ah / 9 × 1P416S
Battery voltage range1040–1518.4 V
Rated grid voltage550 V
Rated grid frequency50 Hz
IsolationTransformer isolation
Battery container dimensions13106 × 2896 × 2438 mm
Power-conversion container dimensions6058 × 2896 × 2438 mm
External communicationsEthernet / Modbus TCP / IEC 104
CoolingAir cooling

Units: W / kW = power; Wh / kWh = stored energy; kVA = apparent power and is not interchangeable with kW. V = voltage; A = current; Ah = charge capacity.

This is a megawatt-scale project system. Define delivered equipment, grid interface, protection and fire safety in the project design. Rated energy does not guarantee usable energy or fixed runtime.

Applications

Factory energy management

Develop operating schedules from the load profile and tariff structure.

Solar and wind storage

Size storage against generation, connection and dispatch requirements.

System integration projects

Coordinate the battery, PCS, transformer and site works.

Battery and system safety

System safety brings together battery management, overcurrent protection, isolation, thermal control and the installation environment. Electrical connection, earthing and commissioning require suitably qualified personnel.

Operate within the selected model’s voltage, current and temperature limits. Site protection, fire safety and grid requirements are addressed in the project design.

Certification and export documentation

Include the sales country, installation setting and shipping method in your enquiry. HSY can then coordinate the compliance, test and transport documentation required for the configuration.

Certificates and test documents must cover the actual model and delivered configuration. Project compliance requires the applicable documentation.

Discuss your OEM/ODM project

Importers, distributors and project buyers can discuss branding, packaging, destination-market requirements, connections and system integration. HSY will review configuration, documentation and supply scope for the project.

Share the target configuration, volume and required timing to receive a comparable proposal. Customization feasibility and commercial terms are defined in the quotation.

Request a quote ↗

Configuration options

ConfigurationBattery energyConfiguration detail
M33553355 kWh1.72 MW AC
HSY-1044K-F ↗1044 kWh500 kVA AC

Procurement FAQ

How are containers and equipment scoped in a quotation?

The specification lists separate battery and power-conversion containers. Define whether the transformer, PCS, distribution, fire protection, installation and commissioning are included in the quotation.

Is this another HSY-1044K-F configuration?

This 3.355MWh, 1.72MW container system is separate from HSY-1044K-F. Use the load profile, connection voltage and site conditions to define the solution; nominal energy alone does not guarantee runtime.

How should I match the electrical configuration?

This is a megawatt-scale project system. Define delivered equipment, grid interface, protection and fire safety in the project design. Rated energy does not guarantee usable energy or fixed runtime.

What should I include in an enquiry?

Include country, configuration, quantity, loads and OEM/ODM requirements. For system projects, also provide electrical drawings, site conditions and grid requirements.

Can documentation be matched to my market?

List the required standards, test reports and transport documents. Their scope must match the selected model, configuration and destination.

Tell us about your project

HSY / HAOSHENG

M3355 1.72MW / 3.355MWh Container Energy Storage System

Preparing or copying does not send an enquiry. Review the text before sending it through email or WhatsApp.

Send an enquiry with the HSY online form ↗

IP Geolocation by DB-IP